EtherTRAK-2 Fault Tolerant I/O

E2/EB-XXX

 

Finally! Fault-tolerant I/O to make your job easier!
Real-time Ethernet Ring - Redundant Power Survivability - Self-Resetting Fuses
Independent Watchdog/Health Monitoring - "Undo" Web Features and much more.

EtherTRAK-2 is our truly rugged breakthrough product packed with innovations that are revolutionizing process control systems. Explore the next generation of "Process Quality I/O". They offer the ultimate price/performance for the process control industry with self-contained I/O modules that integrate with any control system.

Sixnet knows industrial –
Our 30-year track record as the #1 supplier of industrial equipment for extreme environments says it all. As a Total Quality supplier of reliable, ever improving products built for the most rugged applications on the planet, our newest generation of I/O will exceed expectations.


PRODUCT HIGHLIGHTS

  • Module Health Reporting on the operational status of the I/O module itself.
  • Hot swap for instant installation and maintenance
  • Self-resetting fuses protect I/O against short circuits
  • Fast analog inputs report time integrated, and very stable 16 bit results.
  • Web-based I/O configuration and monitoring.
  • Stores project documentation in a quick-access web server.
  • Easy to view LEDs provide complete status info.
  • OEM customizable components and labeling, web pages can include your logo and identification, part numbers, etc.
  • I/O Concentrator can poll other Modbus or Sixnet I/O devices and report I/O status of as many as 512 discrete and 256 analog registers from 16 remote devices.
  • Time proportioned outputs can be configured to pulse on with a duty cycle proportional to analog output register.
  • 20 year support policy – making your job easier forever!

HIGH PERFORMANCE, FLEXIBLE I/O

  • 32 I/O channels in a space-saving package
  • Flexible mix of functions in a single module
  • 16 bit analog for extreme accuracy
  • 1 mS I/O polling for lightning fast performance
  • Advanced counter functions with 32 bit reporting
  • Watchdog monitoring and reportingSmall, modular footprint - just 9 cm on a DIN rail
FLEXIBLE, REDUNDANT, "MULTIPORT" COMMUNICATIONS
  • Dual Ethernet ports eliminate a need for switches
  • Real-time Ring™ Switch for fault-tolerant redundancy
  • Power over Ethernet reduces cabling & costs
  • RS485, USB & optional RS232 ports for flexibility
  • Supports industry standard Modbus messaging
  • Embedded I/O concentrator polls additional I/O
EXTRAORIDNARY FEATURES MAKE YOUR JOB EASIER
  • Web-based I/O configuration and monitoring
  • Stores project documentation in a quick-access web server
  • Hot swap for instant installation and maintenance
  • OEM customizable components and labeling
  • Vibration tolerant, space saving package
TRUE INDUSTRIAL DESIGN
  • Industrial -40 to +75°C operating range
  • UL / CSA (CUL), FCC and CE rated ... More info
  • Hazardous locations rated for Class I, Div. 2 (Zone 2) areas
  • Unique 20-year support and service policy

GENERAL I/O MODULE CHARACTERISTICS
  • Power supply voltage: 10-30 VDC
  • Input current requirement: 75 mA @ 24 VDC typical w/ no loads
  • Etherbus®  PoE power (EB- only) 10 Watts at 60°C for user loads
  • De-rate to 5 Watts at 75°C
  • I/O registers available for addnl expansion  I/O: 512 discrete inputs and outputs plus
  • 256 analog inputs and output registers
  • Unique station addresses 16,000+ (Sixnet or 247 Modbus)
ETHERNET – 2 PORTS
  • Ethernet Port(s): 10/100BaseTx (auto-detecting)
  • Connection: RJ45 (auto-crossover)
  • Isolation: 1500 Volts RMS 1 minute (60 Hz.)
  • Message response time is less than 1 mS per message 
  • Diagnostic LED’s, solid indicates link, blinking indicates activity
  • Protocols supported:  TCP/IP, ARP, UDP, ICMP, DHCP, Modbus/TCP, SIXNET, & more
  • Real-time Ring™ 5ms per hop recovery time
  • Independent networks, 1 or 2 with unique MAC & IP address
SERIAL PORTS
  • RS485 port, Screw terminals (485+, 485-, GND) (2-wire half-duplex, not isolated)
  • RS485 networking, Up to 32 (full-load) stations
  • RS485 distance, Up to 0.5 miles (baud rate dependant)
  • Baud Rates from 300 to 57,600 baud
  • RS232 Port (optional) (TD, RD, CTS, RTS, GND)
  • 2nd RS232 Port (special order) RJ45 (TD, RD, CTS, RTS, CD, DTR, DSR, GND)
  • Protocols: master & slave: SIXNET & Modbus RTU/ASCII
  • Diagnostic LEDs: Transmit (TD) & Receive (RD)
  • Flow Control, RTS-party (for radios and RS485)
WEB INTERFACE
  • Secure Web Access with Password protection for multiple users
  • 1 Simultaneous User
  • 750K  Memory for User Pages (more with special order)
ENVIRONMENTAL
  • Mounting DIN rail (EN50022) or direct to panel or flat panel mount
  • Operating temperature of -40 to 75°C (-40 to 85°C storage)
  • Humidity 5 to 95% RH (non-condensing) (optional conformal coating)
  • Flammability UL 94V-0 materials
  • Electrical Safety UL 508, CSA C22.2/14; EN61010-1 (IEC1010); CE
  • EMI emissions FCC part 15, ICES-003, Class A; EN55022; EN61326-1; CE
  • EMC immunity EN61326-1 (EN61000-4-2,3,4,6); CE
  • Surge withstand IEEE-472 (ANSI C37.90)
  • Vibration: IEC68-2-6 
  • Hazardous locations (Class 1, Div 2, Groups A, B, C, D) UL 1604, CSA C22.2/213, Cenelec EN50021 Zone 2
  • Marine & offshore tested and/or verified to meet various marine and maritime standards such as DNV No. 2.4, Lloyds & ABS
  • Packaging Impact resistant Lexan® polycarbonate
  • Module & Base: 5.5”L x 3.5”W x 5.1”H (14cm x 8.9cm x 13cm)
DISCRETE INPUT CHANNELS
  • Voltage range E2-16DIAC-D only: 10 – 30 VDC (others on special order) 60 – 140 VAc
  • Input Polarity: Sourcing (apply power to active) or sinking (ground closure) on 8 inputs
  • Input isolation: 150 Volts (16 channel modules only)
  • Guaranteed ON voltage: 9 VDC (55 VAC – AC module)
  • Guaranteed OFF voltage: 5.0 VDC (35VAC – AC module)
  • Guaranteed OFF current: 2 mA DC
  • Input resistance: 10 Kohms
  • Input current (@ 24 VDC) 3 mA
  • Filtered ON/OFF delay: 25 mS (20 Hz. max. counting rate)
  • Fastest response: 1 mS (400 Hz. max. counting rate)
  • Special fast counting rate: Up to 50 KHz on channels 1 and 2
  • Count up, pulse timing and pulse rate 16 or 32 bit reporting
  • Scan rate (all channels) 1 mS
DISCRETE OUTPUT CHANNELS
  • Output voltage range 10-30 VDC
  • Max. output per channel ET-16DO24 only: 0.5 Amps
    (ET-MIX… and ET-32DO24) 1 Amp (0.8A above 60°C)
  • Max. output per module: 8 Amps (16 Amps for E2-16DO24)
  • Max. off state leakage: 0.01 mA (less than 10 ?A)
  • Short circuit protection, self-reset fuses (trip above 1.5 Amp)
  • Min. load: 1 mA
  • Inrush current: 5 Amps (100 mS surge)
  • Typical on resistance: 0.3 Ohms (Drop 0.3 VDC @ 1 Amp)
  • Input isolation: 150 Volts (16 channel modules only)
  • All channels Scan rate: 1 mS
ANALOG OUTPUT CHANNELS
  • Analog output range 4-20 mA
  • D/A resolution 16 bits (less than 1 uA)
  • Full scale accuracy  +/-0.02% (at 20°C)
  • Span and offset temp. +/- 50 ppm per °C typ.
  • Max. output settling time 5 mS (to .05%)
  • Load resistance (@ 24 V) 0-750 Ohms
  • Current limiting short circuit protection
ANALOG INPUT CHANNELS
  • Standard ranges 4-20 mA or 0 to +10 VDC
  • A/D resolution 16 bits (0.003%) 10 bits (fast option)
  • Full scale accuracy +/- 0.02% (at 20 °C, 16 bit mode)
  • Temperature coefficient +/- 50 ppm per °C (span and offset)
  • Input impedance (resistance) 100 ohms (4-20 mA input range) 200 Kohms (10 volt input range)
  • Self-resetting short circuit protection fuses (4-20 mA inputs)
  • DMRR (differential mode) 66 db at 50/60 Hz
  • Fastest update time [# of chan.] 880 mS [all] -16-bit; 145ms [all] -14-bit; 1 ms [2] -10-bit

PART NUMBER EtherTRAK-2 with wiring base

PART NUMBER
INCLUDING PoE

DI

DO

AI

AO

DESCRIPTION
E2-MIX24880-D
EB-MIX24880-D
24
8
8
0
Combination I/O with 1 isolated input counter *
E2-MIX24882-D
EB-MIX24882-D
24
8
8
2
Combination I/O with 2 analog outputs **
E2-32DI24-D
EB-32DI24-D
32
 
 
 
32 inputs (10-30 VDC)
E2-16DI24-D
EB-16DI24-D
16
 
 
 
16 individually isolated channels, 10-30 VDC/VAC with counters
E2-16DIAC-D
-
16
 
 
 
16 individually isolated inputs,120 VAC nominal
E2-32DO24-D
EB-32DO24-D
 
32
 
 
High density discrete outputs
E2-16DO24-D
EB-16DO24-D
 
16
 
 
Individually isolated 1 Amp outputs with self-resetting fuses
E2-32AI20M-D
EB-32AI20M-D
 
 
32
 
High density 16 bit 4-20mA inputs with self-resetting fuses
E2-32AI10V-D
EB-32AI10V-D
 
 
32
 
Voltage inputs
E2-16AI20M-D
EB-16AI20M-D
 
 
16
 
16 channels 4-20mA inputs with self-resetting fuses
E2-8AO20M-D
EB-8AO20M-D
 
 
 
8
4-20mA analog outputs
E2-16AI-8AO-D
EB-16AI-8AO-D
 
 
16
8
16 4-20mA inputs plus 8 4-20mA outputs
E2-16ISOTC-D***
EB-16ISOTC-D***
 
 
16TC
 
Instrumentation thermocouples
E2-8ISOTC-D***
EB-8ISOTC-D***
 
 
8TC
 
Instrumentation thermocouples
E2-16ISO20M-D***
EB-16ISO20M-D***
 
 
16
 
Isolated 4-20mA inputs
E2-10RTD-D
EB-10RTD-D
 
 
10
RTD
 
RTD (100 Ohm platinum), -200 to 850°C.

Note: * 24 maximum DI’s are listed, 8 of which can be configured as either DI or DO. The discrete outputs are protected by self-resetting fuses. ** EB part number prefix (above) is for modules that include the optional PoE feature. Standard product part numbers begin with E2. *** Please check factory for availability