Finally! Fault-tolerant I/O to make your job easier!
Real-time Ethernet Ring - Redundant Power Survivability - Self-Resetting Fuses
Independent Watchdog/Health Monitoring - "Undo" Web Features and much more.
EtherTRAK-2 is our truly rugged breakthrough product packed with innovations that are revolutionizing process control systems. Explore the next generation of "Process Quality I/O". They offer the ultimate price/performance for the process control industry with self-contained I/O modules that integrate with any control system.
Sixnet knows industrial –
Our 30-year track record as the #1 supplier of industrial equipment for extreme environments says it all. As a Total Quality supplier of reliable, ever improving products built for the most rugged applications on the planet, our newest generation of I/O will exceed expectations.
PRODUCT HIGHLIGHTS
- Module Health Reporting on the operational status of the I/O module itself.
- Hot swap for instant installation and maintenance
- Self-resetting fuses protect I/O against short circuits
- Fast analog inputs report time integrated, and very stable 16 bit results.
- Web-based I/O configuration and monitoring.
- Stores project documentation in a quick-access web server.
- Easy to view LEDs provide complete status info.
- OEM customizable components and labeling, web pages can include your logo and identification, part numbers, etc.
- I/O Concentrator can poll other Modbus or Sixnet I/O devices and report I/O status of as many as 512 discrete and 256 analog registers from 16 remote devices.
- Time proportioned outputs can be configured to pulse on with a duty cycle proportional to analog output register.
- 20 year support policy – making your job easier forever!
HIGH PERFORMANCE, FLEXIBLE I/O
- 32 I/O channels in a space-saving package
- Flexible mix of functions in a single module
- 16 bit analog for extreme accuracy
- 1 mS I/O polling for lightning fast performance
- Advanced counter functions with 32 bit reporting
- Watchdog monitoring and reportingSmall, modular footprint - just 9 cm on a DIN rail
- Dual Ethernet ports eliminate a need for switches
- Real-time Ring™ Switch for fault-tolerant redundancy
- Power over Ethernet reduces cabling & costs
- RS485, USB & optional RS232 ports for flexibility
-
Supports industry standard Modbus messaging
-
Embedded I/O concentrator polls additional I/O
- Web-based I/O configuration and monitoring
- Stores project documentation in a quick-access web server
- Hot swap for instant installation and maintenance
- OEM customizable components and labeling
- Vibration tolerant, space saving package
- Industrial -40 to +75°C operating range
- UL / CSA (CUL), FCC and CE rated ... More info
- Hazardous locations rated for Class I, Div. 2 (Zone 2) areas
- Unique 20-year support and service policy
- Power supply voltage: 10-30 VDC
- Input current requirement: 75 mA @ 24 VDC typical w/ no loads
- Etherbus® PoE power (EB- only) 10 Watts at 60°C for user loads
- De-rate to 5 Watts at 75°C
- I/O registers available for addnl expansion I/O: 512 discrete inputs and outputs plus
- 256 analog inputs and output registers
- Unique station addresses 16,000+ (Sixnet or 247 Modbus)
- Ethernet Port(s): 10/100BaseTx (auto-detecting)
- Connection: RJ45 (auto-crossover)
- Isolation: 1500 Volts RMS 1 minute (60 Hz.)
- Message response time is less than 1 mS per message
- Diagnostic LED’s, solid indicates link, blinking indicates activity
- Protocols supported: TCP/IP, ARP, UDP, ICMP, DHCP, Modbus/TCP, SIXNET, & more
- Real-time Ring™ 5ms per hop recovery time
- Independent networks, 1 or 2 with unique MAC & IP address
- RS485 port, Screw terminals (485+, 485-, GND) (2-wire half-duplex, not isolated)
- RS485 networking, Up to 32 (full-load) stations
- RS485 distance, Up to 0.5 miles (baud rate dependant)
- Baud Rates from 300 to 57,600 baud
- RS232 Port (optional) (TD, RD, CTS, RTS, GND)
- 2nd RS232 Port (special order) RJ45 (TD, RD, CTS, RTS, CD, DTR, DSR, GND)
- Protocols: master & slave: SIXNET & Modbus RTU/ASCII
- Diagnostic LEDs: Transmit (TD) & Receive (RD)
- Flow Control, RTS-party (for radios and RS485)
- Secure Web Access with Password protection for multiple users
- 1 Simultaneous User
- 750K Memory for User Pages (more with special order)
- Mounting DIN rail (EN50022) or direct to panel or flat panel mount
- Operating temperature of -40 to 75°C (-40 to 85°C storage)
- Humidity 5 to 95% RH (non-condensing) (optional conformal coating)
- Flammability UL 94V-0 materials
- Electrical Safety UL 508, CSA C22.2/14; EN61010-1 (IEC1010); CE
- EMI emissions FCC part 15, ICES-003, Class A; EN55022; EN61326-1; CE
- EMC immunity EN61326-1 (EN61000-4-2,3,4,6); CE
- Surge withstand IEEE-472 (ANSI C37.90)
- Vibration: IEC68-2-6
- Hazardous locations (Class 1, Div 2, Groups A, B, C, D) UL 1604, CSA C22.2/213, Cenelec EN50021 Zone 2
- Marine & offshore tested and/or verified to meet various marine and maritime standards such as DNV No. 2.4, Lloyds & ABS
- Packaging Impact resistant Lexan® polycarbonate
- Module & Base: 5.5”L x 3.5”W x 5.1”H (14cm x 8.9cm x 13cm)
- Voltage range E2-16DIAC-D only: 10 – 30 VDC (others on special order) 60 – 140 VAc
- Input Polarity: Sourcing (apply power to active) or sinking (ground closure) on 8 inputs
- Input isolation: 150 Volts (16 channel modules only)
- Guaranteed ON voltage: 9 VDC (55 VAC – AC module)
- Guaranteed OFF voltage: 5.0 VDC (35VAC – AC module)
- Guaranteed OFF current: 2 mA DC
- Input resistance: 10 Kohms
- Input current (@ 24 VDC) 3 mA
- Filtered ON/OFF delay: 25 mS (20 Hz. max. counting rate)
- Fastest response: 1 mS (400 Hz. max. counting rate)
- Special fast counting rate: Up to 50 KHz on channels 1 and 2
- Count up, pulse timing and pulse rate 16 or 32 bit reporting
- Scan rate (all channels) 1 mS
- Output voltage range 10-30 VDC
-
Max. output per channel ET-16DO24 only: 0.5 Amps
(ET-MIX… and ET-32DO24) 1 Amp (0.8A above 60°C) - Max. output per module: 8 Amps (16 Amps for E2-16DO24)
- Max. off state leakage: 0.01 mA (less than 10 ?A)
- Short circuit protection, self-reset fuses (trip above 1.5 Amp)
- Min. load: 1 mA
- Inrush current: 5 Amps (100 mS surge)
- Typical on resistance: 0.3 Ohms (Drop 0.3 VDC @ 1 Amp)
- Input isolation: 150 Volts (16 channel modules only)
- All channels Scan rate: 1 mS
- Analog output range 4-20 mA
- D/A resolution 16 bits (less than 1 uA)
- Full scale accuracy +/-0.02% (at 20°C)
- Span and offset temp. +/- 50 ppm per °C typ.
- Max. output settling time 5 mS (to .05%)
- Load resistance (@ 24 V) 0-750 Ohms
- Current limiting short circuit protection
- Standard ranges 4-20 mA or 0 to +10 VDC
- A/D resolution 16 bits (0.003%) 10 bits (fast option)
- Full scale accuracy +/- 0.02% (at 20 °C, 16 bit mode)
- Temperature coefficient +/- 50 ppm per °C (span and offset)
- Input impedance (resistance) 100 ohms (4-20 mA input range) 200 Kohms (10 volt input range)
- Self-resetting short circuit protection fuses (4-20 mA inputs)
- DMRR (differential mode) 66 db at 50/60 Hz
- Fastest update time [# of chan.] 880 mS [all] -16-bit; 145ms [all] -14-bit; 1 ms [2] -10-bit
PART NUMBER EtherTRAK-2 with wiring base |
PART NUMBER INCLUDING PoE |
DI |
DO |
AI |
AO |
DESCRIPTION |
|
E2-MIX24880-D |
EB-MIX24880-D |
24 |
8 |
8 |
0 |
Combination I/O with 1 isolated input counter * |
|
E2-MIX24882-D |
EB-MIX24882-D |
24 |
8 |
8 |
2 |
Combination I/O with 2 analog outputs ** |
|
E2-32DI24-D |
EB-32DI24-D |
32 |
|
|
|
32 inputs (10-30 VDC) |
|
E2-16DI24-D |
EB-16DI24-D |
16 |
|
|
|
16 individually isolated channels, 10-30 VDC/VAC with counters |
|
E2-16DIAC-D |
- |
16 |
|
|
|
16 individually isolated inputs,120 VAC nominal |
|
E2-32DO24-D |
EB-32DO24-D |
|
32 |
|
|
High density discrete outputs |
|
E2-16DO24-D |
EB-16DO24-D |
|
16 |
|
|
Individually isolated 1 Amp outputs with self-resetting fuses |
|
E2-32AI20M-D |
EB-32AI20M-D |
|
|
32 |
|
High density 16 bit 4-20mA inputs with self-resetting fuses |
|
E2-32AI10V-D |
EB-32AI10V-D |
|
|
32 |
|
Voltage inputs |
|
E2-16AI20M-D |
EB-16AI20M-D |
|
|
16 |
|
16 channels 4-20mA inputs with self-resetting fuses |
|
E2-8AO20M-D |
EB-8AO20M-D |
|
|
|
8 |
4-20mA analog outputs |
|
E2-16AI-8AO-D |
EB-16AI-8AO-D |
|
|
16 |
8 |
16 4-20mA inputs plus 8 4-20mA outputs |
|
E2-16ISOTC-D*** |
EB-16ISOTC-D*** |
|
|
16TC |
|
Instrumentation thermocouples |
|
E2-8ISOTC-D*** |
EB-8ISOTC-D*** |
|
|
8TC |
|
Instrumentation thermocouples |
|
E2-16ISO20M-D*** |
EB-16ISO20M-D*** |
|
|
16 |
|
Isolated 4-20mA inputs |
|
E2-10RTD-D |
EB-10RTD-D |
|
|
10 RTD |
|
RTD (100 Ohm platinum), -200 to 850°C. |
Note: * 24 maximum DI’s are listed, 8 of which can be configured as either DI or DO. The discrete outputs are protected by self-resetting fuses. ** EB part number prefix (above) is for modules that include the optional PoE feature. Standard product part numbers begin with E2. *** Please check factory for availability