A Powerful Solution for Remote Site
Management
IPm2m® is an innovative combination of RTU (Remote Terminal Unit), datalogger, real-time database client, and telemetry interface in a compact installation-ready package,and features rugged flexible performance.
Product Highlights
- Internet/Intranet connectivity (Ethernet and wireless)
- Easy to configure datalogger
- Advanced control capability
- Advanced communications
- Modbus
- DNP3
- SNMP
- PPP
- Hart
- TCP
- ASCII
- RTU...and more
- Highly scalable with additional I/O modules
- 26 I/O channels including counters and 16 bit analog
- OEM packaging available
- Flexible open source Linux Software
Performance Specifications
-
Industrial power PC (32 bit data bus)
-
Operating system embedded Linux
-
Dynamic memory (RAM) 32 Mbytes - 32bit, 0 wait states
-
Program memory (Flash) 32 Mbytes
-
Retained memory (RAM) 512K (battery-backed)
-
Local I/O (on-board) 26 (see ordering info.)
-
I/O Expansion (up to 256) RS485 or Ethernet
-
Datalogging support
-
IEC 61131 programming
-
High Level C programming, Linux open source
Ethernet Port
-
10/100BaseTx (auto-detecting)
-
RJ45 connection (auto-crossover)
-
Protocols TCP/IP, ARP, UDP, ICNP, DHCP, Modbus/TCP, SIXNET, and more
Serial Port
-
RS485 port A screws (485+, 485-, GND)
(2-wire half-duplex)
-
RS232 Port B RJ45
(TD, RD, CTS, RTS, CD, DTR,DSR, GND)
-
Protocols (master and slave) Sixnet and Modbus RTU/ASCII;
many others available in Linux
-
Flow control hardware, software, RTS-party
(for radios and RS485)
Discrete Inputs
-
12 channels (sinking or sourcing)
-
Guaranteed ON voltage 9 VDC
-
Maximum voltage 30 VDC
-
Guaranteed OFF voltage and current 5.0 VDC and 1.5 mA DC
-
Input resistance 10K Ohms
-
Input current @ 24 VDC 3 mA
-
Filtered ON/OFF delay 25 mS (20 Hz max. counting)
-
Fast ON/OFF delay 4 mS (100 Hz max. counting)
-
Count rate (channels 1 - 8) see above
(10 KHz on channel 1)
Discrete Outputs
-
4 channels (10-30 VDC)
-
Maximum output per channel 1 Amp
-
Maximum output per module 4 Amps
-
Max. OFF state leakage 0.05 mA
-
Minimum load 1 mA
-
Inrush current 5 Amps (100 mS surge)
-
Typical ON resistance 0.3 Ohms
-
Typical ON voltage (@1A) 0.3 VDC
Analog Inputs
-
8 channels (4-20 mA)
-
A/D resolution 16 bits (0.003%)
-
Full scale accuracy +/-0.1% (@20°C)
-
Span and offset temp. coef. +/-50 ppm per °C
-
Input impedance 100 Ohm
-
Current protection Self-resetting fuses
-
DMRR (differential mode rejection) 66 dB at 50/60 Hz
Analog Outputs
-
up to 2 channels (4-20 mA)
-
D/A resolution 16 bits (less than 1 mA)
-
Full scale accuracy (@20°C) +/- 0.02%
-
Span and offset temp. coef. +/- 50 ppm per °C typical
-
Max. output settling time 5 mS (to .05%)
-
Load resistance range (@ +24 VDC supply) 0-750 Ohms
-
Short circuit protection current limiting
Environmental
-
DIN rail or flat panel mount
-
Input power 10-30 VDC
-
Input current 100 mA @ 24 VDC (typical)
-
Temperature -40 to 70°C (-40 to 85°C storage)
-
Humidity 5% to 95% RH (non-condensing)
-
Flammability UL 94V-0 materials
-
Electrical safety UL 508, CSA C22.2/14; EN610101; (IEC1010)
-
EMI emissions FCC part 15, ICES-003,
Class A; EN55022; EN61326-1
-
EMC immunity EN61326-1 (EN61000-4-2,3,4,6)
-
Surge withstand IEEE-472 (ANSI C37.90)
-
Vibration IEC68-2-6
-
Hazardous locations (Class 1, Div 2, Groups A,B,C,D)
UL 1604, CSA C22.2/213, Cenelec EN50021 Zone 2
-
Tested to Marine/offshore standards
Expand the amount of I/O used in your RTU system using Sixnet I/O modules.
EtherTRAK-2: Fault-tolerant I/O with dual Ethernet ports and Sixnet's patented ring technology.
EtherTRAK: The original Ethernet I/O modules that provide a easy to add I/O to any network
RemoteTRAK I/O: Module product line with an RS485 port for easy expandability locally or over long distances
|
|
8, 10-30VDC discrete inputs, field wiring |
|
|
8, 10-30VDC discrete inputs, universal wiring |
|
|
16, 10-30VDC discrete inputs, high density |
|
|
8, 10-30VDC discrete outputs, field wiring |
|
|
16, 10-30VDC discrete outputs, high density |
|
|
8, 4-20mA analog inputs, 16-bit resolution |
|
|
16, 4-20mA analog inputs, 16-bit resolution, high density |
|
|
8, instrumentation inputs, (thermocouples, Volt, 4-20mA, etc.) |
|
|
4, 4-20mA analog outputs, 13-bit resolution |
|
|
4, 4-20mA analog outputs, 13-bit resolution |
|
|
4,10-30VDC discrete inputs and 4-20mA analog inputs |
|
|
4,10-30VDC discrete inputs and discrete outputs |
|
|
Low Cost RTU, mix of discrete ins and outs, and analog ins.
|
How Much Datalogged Information Can be Stored?
Each Sixlog file is allocated a fixed amount of memory. Each record typically contains a time stamp (4 bytes), analog values (2 bytes each), and discrete values (8 per byte). The size of the record is automatically computed and displayed for you by the Sixlog software. The overall storage time (until the oldest data in a full file is overwritten by new data) is computed as:
Longest storage = (file size) x (capture interval) / (bytes per record)
Example:
-
16 analog values plus a time stamp ( 32 + 4 = 36 bytes) are logged every 5 minutes into a 400K file.
-
Oldest data = 400,000 (approx) x 5 minutes / 36 bytes/record = 55,555 Minutes (38 days)
By default, the VT-MIPM / mIPm+ has more than 400K for datalogging.
Adding I/O to a Mini-VersaTRAK mIPm / mIPm+
-
Any combination of EtherTRAK-2 , EtherTRAK and RemoteTRAK I/O modules can be connected to a Mini-VersaTRAK mIPm / mIPm+.
-
A single Mini-VersaTRAK mIPm / mIPm+ supports up to 256 EtherTRAK and/or RemoteTRAK I/O.
Why Mini-VersaTRAK mIPm Instead of other Sixnet Controllers?