The Ultimate Truly Open RTU - Complete with 26 On-board I/O The Mini-VersaTRAK mIPm seamlessly integrates into Scalable Control Systems (SCS)
Limitless Communications; from Ethernet to radios, there is no limit to the flexibility and power of SIXNET's Mini-IPm Open RTU.
PRODUCT HIGHLIGHTS
ADVANCED SOFTWARE FEATURES
- Flexible open-source LINUX software
- Powerful C/C++ programming
- ISaGRAF IEC 61131 programming
- Datalogging & alarming
- Peer to peer I/O transfer capability
- IPm Add-on Applications
- + AGA, DNP3, SNMP, PPP, Hart & more
- + AGA & DNP3 come standard on the mIPm+
- Other automation and control features
- Advanced security capabilities
- Up to 5 com ports (1 Ethernet and 4 serial)
- Limitless multi-user connectivity supports Internet, telephone, wireless and more
- Modbus TCPIP, UDP, ASCII, & RTU
- Advanced communications capabilities
- -40 to +70°C operating temperature
- UL, CSA, CE, DNV, & Zone 2 rated
PERFORMANCE SPECIFICATIONS
- Industrial powerPC (32 bit data bus)
- Operating system embedded Linux
- Dynamic memory (RAM) 16 Mbytes - 32bit, 0 wait states
- Program memory (Flash) 16 Mbytes
- Retained memory (RAM) 512K (battery-backed)
- Local I/O (on-board) 26 (see ordering info.)
- I/O Expansion (up to 256) RS485 or Ethernet
- Datalogging support
- IEC 61131 programming
- High Level C programming, Linux open source
- 10/100BaseTx (auto-detecting)
- RJ45 connection (auto-crossover)
- Protocols TCP/IP, ARP, UDP, ICNP, DHCP, Modbus/TCP, SIXNET, and more
- RS485 port A screws (485+, 485-, GND) (2-wire half-duplex)
- RS232 Port B RJ45 (TD, RD, CTS, RTS, CD, DTR,DSR, GND)
- RS485 Port C (optional) Screws (485+, 485-, GND) (2-wire half-duplex)
- RS232 Port D Screws (TD, RD, RTS, GND)
- Protocols (master & slave) SIXNET & Modbus RTU/ASCII; many others available in Linux
- Flow control hardware, software, RTS-party (for radios and RS485)
- 12 channels (sinking or sourcing)
- Guaranteed ON voltage 9 VDC
- Maximum voltage 30 VDC
- Guaranteed OFF voltage & current 5.0 VDC & 1.5 mA DC
- Input resistance 10K Ohms
- Input current @ 24 VDC 3 mA
- Filtered ON/OFF delay 25 mS (20 Hz max. counting)
- Fast ON/OFF delay 4 mS (100 Hz max. counting)
- Count rate (channels 1 - 8) see above (10 KHz on channel 1)
- 4 or 8 channels (10-30 VDC)
- Maximum output per channel 1 Amp
- Maximum output per module 8 Amps
- Max. OFF state leakage 0.05 mA
- Minimum load 1 mA
- Inrush current 5 Amps (100 mS surge)
- Typical ON resistance 0.3 Ohms
- Typical ON voltage (@1A) 0.3 VDC
- 6 or 8 channels (4-20 mA)
- A/D resolution 16 bits (0.003%)
- Full scale accuracy +/-0.1% (@20°C)
- Span and offset temp. coef. +/-50 ppm per °C
- Input impedance 100 Ohm
- Current protection Self-resetting fuses
- DMRR (differential mode rejection) 66 dB at 50/60 Hz
- up to 2 channels (4-20 mA)
- D/A resolution 16 bits (less than 1 mA)
- Full scale accuracy (@20°C) +/- 0.02%
- Span and offset temp. coef. +/- 50 ppm per °C typical
- Max. output settling time 5 mS (to .05%)
- Load resistance range (@ +24 VDC supply) 0-750 Ohms
- Short circuit protection current limiting
- DIN rail or flat panel mount
- Input power 10-30 VDC
- Input current 100 mA @ 24 VDC (typical)
- Temperature -40 to 70°C (-40 to 85°C storage)
- Humidity 5% to 95% RH (non-condensing)
- Flammability UL 94V-0 materials
- Electrical safety UL 508, CSA C22.2/14; EN610101; (IEC1010)
- EMI emissions FCC part 15, ICES-003, Class A; EN55022; EN61326-1
- EMC immunity EN61326-1 (EN61000-4-2,3,4,6)
- Surge withstand IEEE-472 (ANSI C37.90)
- Vibration IEC68-2-6
- Hazardous locations (Class 1, Div 2, Groups A,B,C,D) UL 1604, CSA C22.2/213, Cenelec EN50021 Zone 2
- Tested to Marine/offshore standards
EtherTRAK: The original Ethernet I/O modules that provide a easy to add I/O to any network
8, 10-30VDC discrete inputs, field wiring
How Much Datalogged Information Can be Stored?
Each Sixlog file is allocated a fixed amount of memory. Each record typically contains a time stamp (4 bytes), analog values (2 bytes each), and discrete values (8 per byte). The size of the record is automatically computed and displayed for you by the Sixlog software. The overall storage time (until the oldest data in a full file is overwritten by new data) is computed as:
Longest storage = (file size) x (capture interval) / (bytes per record)
Example:
- 16 analog values plus a time stamp ( 32 + 4 = 36 bytes) are logged every 5 minutes into a 400K file.
- Oldest data = 400,000 (approx) x 5 minutes / 36 bytes/record = 55,555 Minutes (38 days)
By default, the VT-MIPM / mIPm+ has more than 400K for datalogging.
Adding I/O to a Mini-VersaTRAK mIPm / mIPm+
Any combination of EtherTRAK-2 , EtherTRAK and RemoteTRAK I/O modules can be connected to a Mini-VersaTRAK mIPm / mIPm+. A single Mini-VersaTRAK mIPm / mIPm+ supports up to 256 EtherTRAK and/or RemoteTRAK I/O.
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||